Performance Data
All performance data is supplied in accordance with BS EN 14511-1:2013
OPERATING LIMITS
(For 100% Water)
Minimum Ambient Air DB °C
-5°C
Maximum Ambient Air DB °C
Refer to
Minimum Leaving Water Temperature °C
+5°C
Maximum Return Water Temperature °C
+20°C
1
Temperatures lower than those stated can be obtained with the addition of glycol.
2
For conditions outside those quoted, please refer to Airedale.
GLYCOL DATA
Glycol is recommended when a supply water temperature of +5°C or below is required or
when static water can be exposed to freezing temperatures.
Ethylene Glycol Nominal Correction Factors
Glycol in System / Freezing
Point ºC
10% / -4°C
20% / -9°C
30% / -15°C
40% / -23°C
Cooling Duty
x by
0.98
0.97
0.95
0.93
Input Power
0.99
0.98
0.96
0.95
Water Flow
0.99
1.02
1.04
1.07
Pressure Drop
1.05
1.20
1.38
1.57
Propylene Glycol Nominal Correction Factors
Glycol in System / Freezing
Point ºC
10% / -2°C
20% / -6°C
30% / -12°C
40% / -20°C
Cooling Duty
x by
0.97
0.95
0.91
0.88
Input Power
0.99
0.98
0.96
0.95
Water Flow
0.98
0.97
0.95
0.95
Pressure Drop
1.08
1.17
1.31
1.45