Ultima ™ remote air cooled chillers, General specification – Airedale Ultima Remote Air Cooled 75kW - 450kW User Manual
Page 24
![background image](/manuals/370946/24/background.png)
ULTIMA
™ REMOTE AIR COOLED
Chillers
24
Chillers
Technical Manual : Part No 6259485 V1.6.0_07_2014
General Specification
ELECTRICAL DATA
URAC200
URAC225
UWC240
URAC250
UWC270
Unit Data
Nominal Run Amps
(1)
A
101
115
120
129
141
Maximum Start Amps
(2)
A
301
355
298
369
314
Permanent Supply
VAC
230V 1PH 50Hz
Mains Supply
VAC
400V 3PH 50Hz
Rec Permanent Fuse Size
A
16
16
16
16
16
Rec Mains Fuse Size
A
160
160
160
200
200
Max Permanent Incoming Cable
Size
mm²
4 mm² terminals
Max Mains Incoming Cable Size
mm²
70 (direct to MCCB)
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
100
100
100
100
100
External Trace Heating
Available (fitted by others)
W
500
500
500
500
500
Compressor - Per Compressor
Quantity
4
2+2
3+3
4
3+3
Motor Rating
kW
14.4
14.4/17.9
10.9/10.9
17.9
10.9/14.4
Nominal Run Amps
(1)
A
25.2
25.2/32.2
20.0/20.0
32.2
20.0/25.2
Crankcase Heater Rating
W
120.0
120.0/150.0
70.0/70.0
150.0
70.0/120.0
Start Amps
(2)
225
225/272
198/198
272
198/225
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Nominal Run Amps
(1)
A
90
103
112
115
126
Maximum Start Amps
(2)
A
293
346
288
358
301
Recommended Mains Fuse
A
125
160
125
160
160
Compressor Nominal Run
Amps - Per Compressor
A
22.5
22.5/28.8
17.9/17.9
28.8
17.9/22.5
Electronic Soft-Start
Nominal Run Amps
(1)
A
101
115
120
129
141
Maximum Start Amps
(2)
A
211
246
219
260
234
Recommended Mains Fuse
A
160
160
160
200
200
(1)
Based at 12/7°C water and 45°C dew point
(2)
Starting amps refers to the direct on line connections.