Chillers ultima ™ remote air cooled, Design features & information – Airedale Ultima Remote Air Cooled 75kW - 450kW User Manual
Page 13
![background image](/manuals/370946/13/background.png)
Chillers
ULTIMA
™ REMOTE AIR COOLED
Chillers
13
Technical Manual : Part No 6259485 V1.6.0_07_2014
Design Features & Information
- CONTROLS
FEATURES
Temperature
The microprocessor maintains the set supply Chilled Water temperature by sensing the
return and supply water temperatures, compressor loading.
The microprocessor also monitors and displays the following measured parameters:
Supply Water Temperature
Return Water Temperature
Suction Pressure of each circuit
Liquid Pressure of each circuit
Suction Temperature at each circuit
Superheat for each circuit
Alarms
The following conditions will be detected, triggering a visual display:
Common for both circuits:
Low Supply Temperature
Emergency Stop
Water Flow
Individual for each circuit:
Individual alarms will isolate the affected circuit only.
Compressor Trip
Low Suction Pressure for each circuit
High Liquid Pressure for each circuit
Volt Free Contact Alarm Indication
Low Pressure Switch
Compressor Overload
High Compressor Discharge Temperature
Networking
A Local Area Network (
) can be used to connect a number of chiller controllers to
offer intercommunication and sequence control. This also allows the connection of
computers, printers and modems on the same communications ring. For further details
and quotation, please contact Airedale Controls.