ALARM (FB-Nr.: 70 ... 77 Typ-Nr.: 46)
Function block ‘ALARM’ defines the overall alarm processing of the relevant controller. The data are
provided once per controller channel.
Process data
General
(Function no.: 0)
Code Des.
R/W Type
Description
Range
Rem.
00
Block
R
Block
Block access (1 .. 3)
1
Status_Al1 R
ST1
Alarm status 1
A
2
Status_Al2 R
ST1
Heating current alarm
B
3
HC
R
BCD
Heating current meas. value
18
Type
R
INT
Type no. of function block
46
Bem. A Status_Al1
MSB
LSB
D7
D6
D5
D4
D3
D2
D1
D0
Bit no.
Name
Allocation
Status ‘0’
Status ‘1’
D0
Lim HH
Alarm HH
off
on
D1
Lim H
Alarm H
off
on
D2
Lim L
Alarm L
off
on
D3
Lim LL
Alarm LL
off
on
D4
Fail
Fail
no
yes
D5
‘0’
Always ‘0’
D6
‘1’
Always ‘1’
D7
Parity
Bem. B Status_Al2
MSB
LSB
D7
D6
D5
D4
D3
D2
D1
D0
Bit-Nr.
Name
Allocation
Status ‘0’
Status ‘1’
D0
HCAl
Heating current alarm channel
off
on
D1
LeckAl
Leakage current alarm channel
off
on
D2
do1_8Al
Output alarm do1..do8
off
on
D3.. D5 ‘0’
Always ‘0’
D6
‘1’
Always ‘1’
D7
Parity
Parameter a. configuration data
General
(Function no.: 0)
Code
Des.
R/W Type Description
Range
Rem.
B2
41
LimL
R/W BCD Low limit alarm
-999..9999
1)
42
LimH
R/W BCD High limit alarm
-999..9999
43
xsd1
R/W BCD Switching difference low and high alarms
0..9999
44
LimLL R/W BCD Low low limit alarm
-999..9999
1)
45
LimHH R/W BCD High high limit alarm
-999..9999
46
LimHC R/W BCD Heating current limit value
0..HC100
B3
71
C600
R/W INT Src:
signal source
Fnc:
function
DestFail: fail Destination
(T,H)
(Z)
(E)
0..xxyz
72
C601
R/W INT DestLL :
DestL
:
DestH
:
DestHH :
(T)
(H)
(Z)
(E)
0..wxyz
Function block protocol
27
9499 040 49411
1) Datum has switch-off function; additional data value ‘-32000’