CONTR (FB no.: 50 ... 57 Type no.: 91)

All data concerning the controller are grouped in function block ‘CONTR’. They are provided once for each

controller channel.

Process data

General

(Function no.: 0)

Code Des.

R/W

Type

Description

Range

Rem

00

Block

R

Block

Block access (1...9)

1

Status 1

R

ST1

Status 1

A

3

W

R

BCD

Eff. set-point

4

X

R

BCD

Eff. process value

5

Y

R

BCD

Effective output variable

6

xw

R

BCD

Control deviation

18

Type

R

INT

Type no. of function block

90

20

Block

L

Block

Blockzugriff (21...26)

21

Xeff

L

FP

eff. Istwert

22

Yeff

L

FP

wirksame Stellgröße

23

HC

L

FP

Heizstrommeßwert

24

Unit_State L

ICMP

Eingangswerte (di)

Ä Seite

25

Alarm_x

L

ICMP

Alarmwerte

Ä Seite

26

Status_x

L

ICMP

Statusinformationen

Ä Seite

30

Block

R

Block

Block access (31...38)

33

A/M

R/W

INT

Automatic/manual switch-over

0..1

34

OStart

R/W

INT

Self-tuning start

0..1

35

We/i

R/W

INT

Wext/Wint switch-over

0..1

36

w/W2

R/W

INT

w/W2 switch-over

0..1

38

Coff

R/W

INT

Controller off/on

0..1

Bem. A Status1: (code 01)

MSB

LSB

D7

D6

D5

D4

D3

D2

D1

D0

Bit no.

Name

Allocation

Status ‘0’

Status ‘1’

D0

Y1

Switching output

off

on

D1

Y2

Switching output

off

on

D2

A/M

Autom/manual

Auto

Manual

D3

CFail

Controller status

ok

not ok

D4

Coff

Controller switched off

no

yes

D5

XFail

Sensor Fail

no

yes

D6

‘1’

Always ‘1’

D7

Parity

Set-point

Set-point processing

(Function no.:1)

Code

Des.

R/W

Type

Description

Range

Rem.

00

Block

R

Block

Block access (1, 3)

01

WState

R

ST1

Set-point status

B

03

Wint

R

BCD

Effective internal set-point

30

Block

R

Block

Block access (31...32)

31

Wnvol

R/W

BCD

Int. set-point, non-volatile

-999..9999

32

Wvol

R/W

BCD

Int. set-point, volatile

-999..9999

Bem. B WState: (code 01)

MSB

LSB

D7

D6

D5

D4

D3

D2

D1

D0

Bit no. Name

Allocation

Status ‘0’

Status ‘1’

D0

w/W2

w/W2 switch-over

w

W2

D1

We/Wi

Wext/Wint

Wext

Wint

D2

w/Wanf

w/Wanfahr

w

Wanf

D3

GRW

Gradient function active

no

yes

D4

Weff_fail Error effective set-point

no

yes

D5

‘0’

Always ‘0’

D6

‘1’

Always ‘1’

D7

Parity

Function block protocol