2 code tables 14, 1 structure of configuration words (c.xxxx) 14, 2 instrument (fb no.: 0 type no.: 0) 14 – West Control Solutions KS 800 ISO1745 Interface Manual User Manual
Page 14: 2 instrument (fb no.: 0 type no.: 0), Code tables 5.2.1

5.2
CODE tables
5.2.1
Structure of configuration words (C.xxxx)
The configuration words mentioned in the following code tables are composed of several sections, which can
be transmitted only in common.
The data in the table must be interpreted as follows:
Example (C100): Code Descr. R/W Type Description
Range
71
C100 R/W INT
CFunc: Controller function
Wfunc: set-point function
(T,H)
(E)
0..xxyz
Description
CFunc
WFunc
Thousands
Hundreds
Ones
Range
x
x
z
00 ... 07
0...1
Example: continuous controller; standard controller;
set-point-cascade with offset
0 2 0 4
g
- For transmission of configuration words, see chapter page 29.
- Die Einstellmöglichkeiten der Konfigurationswörter entnehmen Sie der KS 800 Funktionsbeschreibung
(Best. Nr. 9499 040 49218)
5.2.2
INSTRUMENT (FB no.: 0 type no.: 0)
Function block ‘INSTRUMENT’ is used for classification of all data which are valid for the overall instrument.
Process data
General
(function no.: 0)
Code Descr.
R/W Type Description
Range
Rem.
01
Unit_State 1
R
ST1 Status 1
A
10
Block 13..18
R
Block
13
Write Error
R
INT Error during last write access
0, 100...127
Ä p. 11
14
Write Error Position R
INT Position of last write access error
0...99
15
Read Error
R
INT Error of last read access
0, 100...127
16
DPErr
R
INT Error message from DP-module
B
17
DPAdr_eff
R
INT Effectiv PROFIBUS adress
0 … 126
18
Type
R
INT Type no. of function block
0
20
Block 21...27
R
Block
21
HWbas
R
INT Basic HW options: module A, P
C
23
SWopt
R
INT SW options 1
D
24
SWcod
R
INT SW code no. 7th to 10th digit of 12NC
wxyz
E
25
SWvers
R
INT SW code no. 11th to 12th digit of 12NC
00xy
F
26
OPVers
1)
R
INT Operating version
27
EEPVers
1)
R
INT EEPROM version
31
OpMod
R/W INT Switch over unit to configuration mode (only after 1) 0
Switch over unit to on-line mode (only after 0)
1
Cancelation of configuration mode (only after 0)
2
32
Ostartg
R/W INT Self-tuning stop/start of all group controllers
0..1
33
UPD
R/W INT Acknowledgement of local data change
0..1
G
Function block protocol
9499 040 49411
14
1) Data are specified for future use (distinction of internal version).