beautypg.com

Environmental conditions, General, Certifications – West Control Solutions TB 45 Temperature Limiter User Manual

Page 49

background image

ENVIRONMENTAL CONDITIONS

Protection classes

Front panel:

IP 20

Housing:

IP 20

Terminals:

IP 20

Permissible temperatures

For specified accuracy:

-10...55°C

Warm-up time:

ß

20 minutes

Temperature effect:

ß 0,05% / 10 K

Additional effect of CJ compensation:

ß 0,75 K / 10 K

Operating limits:

-20...60°C

For storage:

-30...70°C

Altitude

To 2000 m above sea leveln

Humidity

Max. 95%, 75% yearly average, no condensation

Shock and vibration

Vibration test Fc (DIN EN 60 068-2-6)

Frequency:

10...150 Hz

Unit in operation:

1g or 0,075 mm

Unit not in operation:

2g or 0,15 mm

Shock test Ea (DIN EN 60 068-2-27)

Shock:

15g

Duration:

11ms

Electromagnetic compatibility

Complies with EN 61 326-1 for continuous, unattended operation.

Interference radiation:
Within the limits for Class B devices.
Immunity to interference:
Meets the test requirements for devices in industrial areas.

Evaluation criteria:

w

Surge interference partly has marked effects, which decay after
the interference stops.

w

With high levels of surge interference on 24 VAC mains leads,
it is possible that the device is reset.

w

With HF interference, effects up to 50 µV can occur.

GENERAL

Housing front:

Material

Polyamid PA

6.6

Flammability class:

V0 (UL 94)

Connecting terminals:

Material:

Polyamid PA

Flammability class:

V2 (UL 94) for screw terminals
V0 (UL 94) for spring-clamp terminals
and bus connections

Electrical safety

CE conform
Complies with EN 61 010-1:
Working voltage range 300V, Over-voltage category II,
Contamination degree 2,
Protection class II

Electrical connections

Plug-in connector strips with choice of terminal type:

w

Screw terminals for lead cross-sections from 0,2 to 2,5 mm

2

w

Spring-clamp terminals for lead cross-sections from 0,2 to 2,5 mm

2

Mounting method

Clip-on rail mounting (35 mm top-hat rail to EN 50 022).
Locked by means of metal catch in housing base.
Close-packed mounting possible.

Mounting position:

vertical

Weight:

0,18 kg

Standard accessories

- Operating instructions
- With ‘Interface’ option: bus connector for fitting into top-hat rail

CERTIFICATIONS

• Type tested to EN 14597 (replaces DIN 3440) With certified

sensors applicable for:

– Heat generating plants with outflow temperatures up to

120°C to DIN 4751

– Hot-water plants with outflow temperatures above 110°C to

DIN 4752

– Thermal transfer plants with organic transfer media to DIN

4754

– O

il-heated plants to DIN 4755

Technical data

TB 45