6.7
Maintenance manager / error list
In case of one or several errors, the error list is always displayed at the
beginning of the extended operating level .
A current input in the error list (alarm or error) is always indicated by display
of letter E .
For display of the error list, press key ô once.
E- display
element
Description
Possible remedial action
blinks
Alarm due to existing
error
- Determine the error type in the error list via the error number
- remove error
on
Error removed, Alarm
not acknowledged
- acknowledge alarm in the error list by pressing the È - or the Ì -key
- the alarm entry is deleted by doing so
off
no error, all alarm entrys deleted
6.7.1
Error list::
Name
Description
Cause
Possible remedial action
E.1
Internal error, cannot be
corrected
E.g. defective EEPROM
Contact PMA service
Return device to manufacturer
E.2
Internal error, resettable
E.g. EMC trouble
Keep measuring and supply ca-
bles separate. Protect contactors
by means of RC snubber circuits
E.3
Configuration error, reset-
table
Missing or faulty configuration
Check interdependencies for
configurations and parameters
E.4
Hardware error
Code number and hardware not identical
Contact PMA service
Replace electronics/options card
FbF.1
INP1 sensor break
Defective sensor
Wiring error
Replace INP1 sensor
Check INP1 connection
Sht.1
INP1 short circuit
Defective sensor
Wiring error
Replace INP1 sensor
Check INP1 connection
POL.1
INP1 polarity error
Wiring error
Change INP1 polarity
Lim.1
Latched limit value alarm 1 Adjusted limit value 1 exceeded
Check process
Lim.2 Latched limit value alarm 2
Adjusted limit value 2 exceeded
Check process
Lim.3 Latched limit value alarm 3
Adjusted limit value 3 exceeded
Check process
Inf.1
Time limit value
message
Preset number of operating hours reached
Application-specific
Inf.2 Switching cycle message
(digital outputs)
Preset number of switching cycles reached Application-specific
g
Latched alarms Lim2/3 (E element provided) can be acknowledged and reset via digital input di1 or via the
reset key function. The reset key function can be disabled using a password.
For Configuration, see
ConF / LOGI / Err.r
g
When an alarm is still pending, i.e. unless the error cause was removed (E display blinks), latched alarms
cannot be acknowledged and reset.
Functions
30
Maintenance manager / error list
TB 45
1 2 TB E
450.0
ыC
ььдд
Error-state
Signification
2
Pending error
Change to error status 1after error removal
1
Stored error
Change to error status 0 after acknowledgement in error list 0
0
no error/message
Not visible, except during acknowledgement