Maintenance manager / error list

In case of one or several errors, the error list is always displayed at the
beginning of the extended operating level .

A current input in the error list (alarm or error) is always indicated by display
of letter E .

For display of the error list, press key ô once.

E- display
element

Description

Possible remedial action

blinks

Alarm due to existing
error

- Determine the error type in the error list via the error number
- remove error

on

Error removed, Alarm
not acknowledged

- acknowledge alarm in the error list by pressing the È - or the Ì -key
- the alarm entry is deleted by doing so

off

no error, all alarm entrys deleted

6.7.1

Error list::

Name

Description

Cause

Possible remedial action

E.1

Internal error, cannot be
corrected

E.g. defective EEPROM

Contact PMA service
Return device to manufacturer

E.2

Internal error, resettable

E.g. EMC trouble

Keep measuring and supply ca-
bles separate. Protect contactors
by means of RC snubber circuits

E.3

Configuration error, reset-
table

Missing or faulty configuration

Check interdependencies for
configurations and parameters

E.4

Hardware error

Code number and hardware not identical

Contact PMA service
Replace electronics/options card

FbF.1

INP1 sensor break

Defective sensor

Wiring error

Replace INP1 sensor
Check INP1 connection

Sht.1

INP1 short circuit

Defective sensor

Wiring error

Replace INP1 sensor
Check INP1 connection

POL.1

INP1 polarity error

Wiring error

Change INP1 polarity

Lim.1

Latched limit value alarm 1 Adjusted limit value 1 exceeded

Check process

Lim.2 Latched limit value alarm 2

Adjusted limit value 2 exceeded

Check process

Lim.3 Latched limit value alarm 3

Adjusted limit value 3 exceeded

Check process

Inf.1

Time limit value

message

Preset number of operating hours reached

Application-specific

Inf.2 Switching cycle message

(digital outputs)

Preset number of switching cycles reached Application-specific

g

Latched alarms Lim2/3 (E element provided) can be acknowledged and reset via digital input di1 or via the
reset key function. The reset key function can be disabled using a password.

For Configuration, see

ConF / LOGI / Err.r

g

When an alarm is still pending, i.e. unless the error cause was removed (E display blinks), latched alarms
cannot be acknowledged and reset.

Functions

30

Maintenance manager / error list

TB 45

1 2 TB E

450.0

ыC

ььдд

Error-state

Signification

2

Pending error

Change to error status 1after error removal

1

Stored error

Change to error status 0 after acknowledgement in error list 0

0

no error/message

Not visible, except during acknowledgement