Reset to default

In case of faulty configuration, the device can be
reset to the default manufacturers condition.

1

For this, the operator must keep the keys
increment and decrement pressed during
power-on.

2

Then, press key increment to select

YES

.

3

Press enter to call up the password menu and
to enter the valid password. If the password
is faulty, reset is not possible.

4

Confirm factory resetting with Enter and the
copy procedure is started
(display

COPY

).

5

Afterwards the device restarts.

In all other cases, no reset will occur (timeout
abortion).

g

If one of the operating levels was blocked in BlueControl

Ò

, reset to factory setting is not possible.

g

The copy procedure (

COPY

) can take some seconds.

Now, the transmitter is in normal operation.