beautypg.com

6 analog output configuration 28, 1 analog output (optional) 28, Analog output 28 - 29 – West Control Solutions TB 45 Temperature Limiter User Manual

Page 28

background image

6.6

Analog output configuration

6.6.1

Analog output (optional)

An analog output is available as a display output.

The two output signals (current and voltage) are available simultaneously. Adjust

ConF / Out.3 / O.tYP to se-

lect the output type which should be calibrated.

ConF / Out.3:

O.tYP

=

1

Out.3 0...20mA continuous

=

2

Out.3 4...20mA continuous

=

3

Out.3 0...10V continuous

=

4

Out.3 2...10V continuous

Parameter

O.Src defines the signal source of the output value.

Example:

O.Src =

3

signal source for

Out.3 is

the process value

Scaling of the output range is done via parameters

Out.0 and Out.1. The values are specified in units of the physi-

cal quantity.

Out.0

=

-1999...9999

scaling

Out.3

for 0/4mA or 0/2V

Out.1

=

-1999...9999

scaling

Out.3

for 20mA or 10V

Example: output of the full input range of thermocouple type J (-100 … 1200 °C)

Out.0 = -100
Out.1 = 1200

Example: output of a limited input range, e.g. 60.5 … 63.7 °C)

Out.0 = 60.5
Out.1 = 63.7

+

Please, note: the smaller the span, the higher the effect of input variations and resolution.

g

Using current and voltage output in parallel is possible only in galvanically isolated circuits.

g

Configuration O.tYP = 2 (4 … 20mA) or 4 (2...10V) means only allocation of the reference value (4 mA or 2V)
for scaling of output configuration Out.0. Therefore, output of smaller values is also possible rather than
output limiting by reference value 4mA / 2V.

g

Configuration O.tYP = 0/1 (0/4...20mA) or 2/3 (0/2...10V) determines, which output should be used as a
calibrated reference output.

Functions

28

Analog output configuration

TB 45

phys.

size

mA / V

phys. size

Out.1

Out.0

0/4mA

0/2V

20mA

10V