O.typ, O.act, Lim.2 – West Control Solutions TB 45 Temperature Limiter User Manual
Page 35: Lim.3, Fai.1, Sb.er, Inf.1, Inf.2, Out.0, Out.1
Output Out.2, Out.3
µ
Name
Value range Description
O.tYP
Type of OUT (only Out.3 - analog)
µ
0
Relay/logic
1
0...20 mA continuous
2
4 ... 20 mA continuous
3
0...10 V continuous
4
2...10 V continuous
5
Transmitter supply
O.Act
Direction of operation
0
Direct / normally open
1
Inverse / normally close
Lim.2
Signal limit 2
0
Not active
1
Active
Lim.3
Signal limit 3
0
Not active
1
Active
FAi.1
Signal INP1 fail
0
Not active
1
Active
Sb.Er
System bus error message: internal system bus communication error. The output is
set in case of an error in the internal system bus communication, no communication
with this instrument occurs
0
Not active
1
Active
Inf.1
Message Inf.1 status. The Inf.1 signal is generated, when the limit value for the ope-
rating hours is reached.
0
not active
1
active
Inf.2
Message Inf.2 status. The Inf.2 signal is generated, when the limit value for the num-
ber of switching cycles is reached.
0
not active
1
active
Out.0
-1999...9999 Scaling 0% (only for Out.3 analog)
µ
Lower analog output scaling limit (corresponds to 0%). When using current or volta-
ge signals as output variables, the display values can be scaled to the output values
at parameter level. Specification of the output value of the lower scaling point is in
units of the relevant electrical quantity (mA / V).
Out.1
-1999...9999 Scaling 100% (only for Out.3 analog)
µ
Upper analog output scaling limit (corresponds to 100%). When using current or vol-
tage signals as output variables, the display can be scaled to the output values at pa-
rameter level. Specification of the output value of the upper scaling point is in units
of the relevant electrical quantity (mA / V).
O.Src
Signal source (only for Out.3 analog)
µ
0
Not active
3
Process value
7
INP1
O.FAI
Fail behaviour
µ
0
upscale
1
downscale
Configuration level
TB 45
Configuration
35