beautypg.com

2 configuration 33, Configuration parameter 33 - 38, Configuration – West Control Solutions TB 45 Temperature Limiter User Manual

Page 33: S.typ, S.lin

background image

7.2

Configuration

Dependent on instrument version and configuration settings, display of values which are not required is suppressed.

µ The entries marked with this symbol are selectable only, if the instrument option is fitted.

Inputs InP.1

Name

Value range Description

S.tYP

Sensor type

0

Thermocouple type L (-100...900°C), Fe-CuNi DIN

1

Thermocouple type J (-100...1200°C), Fe-CuNi

2

Thermocouple type K (-100...1350°C), NiCr-Ni

3

Thermocouple type N (-100...1300°C), Nicrosil-Nisil

4

Thermocouple type S (0...1760°C), PtRh-Pt10%

5

Thermocouple type R (0...1760°C), PtRh-Pt13%

6

Thermocouple type T (-200...400°C), Cu-CuNi

7

Thermocouple type C (0...2315°C), W5%Re-W26%Re

8

Thermocouple type D (0...2315°C), W3%Re-W25%Re

9

Thermocouple type E (-100...1000°C), NiCr-CuNi

10

Thermocouple type B (0/100...1820°C), PtRh-Pt6%

18

Special thermocouple (linearization necessary)

20

Pt100 (-200.0 ... 100,0 °C) (150°C with reduced lead resistance)

21

Pt100 (-200.0 ... 850,0 °C)

22

Pt1000 (-200.0...850.0 °C)

23

Special 0...4500 Ohm (preset KTY11-6)

24

Special 0...450 Ohm

25

Special 0...1600 Ohm

26

Special 0...160 Ohm

30

0...20mA / 4...20 mA

40

0...10V / 2...10 V (Inp.1 only)

41

Special (-2,5...115 mV)

42

Special (-25...1150 mV)

43

Special (-25...90 mV)

44

Special (-500...500 mV)

45

Special (-5...5 V) (Inp.1 only)

46

Special (-10...10 V) (Inp.1 only)

47

Special (-200..200 mV)

50

Potentiometer 0...160 Ohm

51

Potentiometer 0...450 Ohm

52

Potentiometer 0...1600 Ohm

53

Potentiometer 0...4500 Ohm

S.Lin

Linearization only adjustable with

S.tYP:18, 23 ... 47

0

none

1

Special linearization. Producing a linearization table is possible via BlueControl (Engi-
neering-Tool). Preset is the characteristic for KTY 11-6 temperature sensors.

Configuration level

TB 45

Configuration

33