The signal data flow of temperature limiter TB 45 is shown in the following diagram:

6.1

Limiting functions

TB 45 can be configured for various functions:

as a temperature limiter

as a temperature monitor

as a limit signaller

6.1.1

Temperature limiter

If selected, a temperature limiter fun ction monitors the process value. When exceeding the (configurable) low or high
limit value LC, the output relay LC is opened and disabled.

Releasing is possible only, when

– the process valueis below the adjusted high limit value LC (minus any adjusted hysteresis) again with setting

Temperature limiter max. (latch)

”, or when the process value is above low limit value LC (plus any adjusted

hysteresis) again with setting “Temperature limiter min. (latch)”.

– reset via digital input di1 or via the reset key combination (selectable) occurred. The reset key combination can

be disabled by means of a password (setting in BlueControl

®

: Configuration / Others / IRES = 1).

g

When display element TB is lit, a temperature limiter function is selected.

a

Please, note that the adjusted filter time

t.F1 can increase the response time for the process value. The

DIN-tested response times were tested with t.F1 = 0,5 s.

Limit values Lim.2, Lim.3 can be used as pre-alarms for (optional) output on OUT.2, OUT.3.