Specifications

Mechanical

Explosion Proof Enclosure:

NFPA (designed to meet)
Class I, Division 1 & 2 Groups B, C and D
Class II, Division 1 & 2 Groups E, F, and G

ATEX EX II2G, NEMKO 02ATEX255
EExd IIB T5 50˚C per En 50-014 & EN50-018

Electrical

Power: 8 VDC Max.
6 x Rechargeable 1.2 VDC NiCad Batteries
Current: 2.5A Avg.
Charge: 400mA for 14 Hours

Environmental

Temperature Range:

-4º F (-20º C) to 122º F (50º C)

Vibration Protection:

1g (10-50hz)

Water and Dust:

IP 67 per EN 60529


Physical

Dimension: 11.5 x 10.1 x 3.9 in (292 x 258 x 100 mm)
Weight: 7.5 lb. (3.4 Kg)

Range*
Sensitivity Range Standard Extended

Range

(with Collimator)

1 (Low)

50 ft (15 m)

3.8 ft (1.2 m)

7 ft (2.2 m)

2

100 ft (30 m)

7 ft (2.2 m)

14.5 ft (4.5 m)

3

150 ft (45 m)

10 ft (3.2 m)

22 ft (7.0 m)

4 (High)

200 ft (60 m)

14.5 ft (4.5 m)

29 ft (9.0 m)


* The minimum distance from the detector is 20 inches (50cm)
* At extreme temperatures - 15% Max. Reduction in range