Spectrex Inc. - SharpEye

TM

CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005

19


E. Electrical outputs

Dry Contact Relays:

Table 11: Contact Ratings

Relay
Name

Type

Normal
position

Maximum Ratings

Alarm

SPDT N.O. N.C. 2A at 30VDC or 0.5A at 250 VAC

Fault *

SPST N.C.

5A at 30VDC or 250 VAC

* The FAULT relay will be normally energised closed during Normal operation of the
detector. The contact will open at ‘Fault’ condition or low voltage.

4-20mA Current Output:

Terminals 11 and 12:

FAULT

0 + 0.5mA

BIT FAULT

2mA±10%

NORMAL 5mA±10%
WARNING 10mA±5%
ALARM

15mA±5%

Communication Network:

The detector is equipped with an RS-485 communication link that can
be used in installations with computerized controllers.

The communicator protocol is compatible with the Modbus
communicator protocol.
• This protocol is a standard and widely used.

• It enables continuous communication between a single standard
Modbus controller (Master device) and a serial Network of up to 247
detectors.
• It enables connection between different types of Spectrex detectors
or other Modbus devices to the same Network.


CCTV Output

The video output is a standard port with two options:

• Detector model No. 20/20 CTIN is a NTSC version

• Detector model No. 20/20 CTIP is a PAL version


The output can be connected to standard video accessories such as a
switching box.