6.8 Operation Mode

When wiring is completed the operational mode can be selected.

Mode selection is achieved through RS-485 using a PC with Spectrex Host
software. Refer to TM784050.

Programmable Function:
Modes of operation are programmable with a PC or Handheld unit according to the
selection table in Paragraph 4.3.1 and Refer to TM 784050. Refer to here in 4.3.1
etc.

Address:
The detector has the capability of acting as an addressable device.
The detector provides 247 addresses, which can be used by the RS-485
communications link as described in paragraph 4.3.4 and Refer to TM 784050.

Alarm Delay:
An Alarm Delay may be required for certain applications. The detector has an
Alarm Delay that permits time delays from 0, anti-flare, 3, 5, 10, 15, 20 and 30
seconds respectively. The delay can be defined by the RS-485. See paragraph
4.3.3 and refer to TM 784050.