6.6 Wiring (Refer to Fig. 11)
1 Disconnect
power.
2 Remove the four (4) protective set-screws from detector front. (Fig. 8 Item 1)
3 Release the four (4) socket-head screws that secure the detector housing
(Item 1) to its back cover (Item 4) Using HEX KEY No. 5. Hold the housing
(Item 1) during the removal of the screws. With the screws removed, pull the
detector housing (Item 1) from its cover (Item 4). The Terminal Board inside
the detector cover is now revealed.
4 Remove the protective plug mounted on the detector conduit inlet / electrical
entry, pull the wires through the detector cover (Item 4) and secure them firmly
to the cover using the cable-clamp (Item 2) attached to it. Use a 3/4"-14NPT
or M25x1.5 explosion-proof conduit /cable gland connection to assemble the
conduit / cable to the detector.
5 Connect the wires to the required terminals (Item 3) according to the wiring
diagram. See paragraph 6.7.
6 Connect the grounding wire to the ground screw outside the detector cover
(Fig. 8 item 2).
The detector must be well grounded to Earth Ground for proper
operation.
7 Verify the wiring. Improper wiring may damage the detector.
8 Check the wires for secure mechanical connection and press them neatly
against the terminal board to prevent them from interfering while closing the