Operating instructions – Spectrex 20/20CTIN-CTIP Flame Detector User Manual
Page 41
Spectrex Inc. - SharpEye
TM
CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005
33
7. Operating Instructions
7.1 Scope
The following instructions are designed to obtain optimal performance from the
detector over its life cycle.
7.2 Power-Up
1 Apply power and wait approximately 60 seconds for the automatic self-test of
the detector.
Note
: Applying power initiates the following sequence:
• POWER LED flashes
• BIT is executed, if successful then:
o
POWER LED turns ON continuous
o
FAULT relay contacts close
2 Wiring Inspection: If a short-circuit or line discontinuity exists, indications will
appear on the control unit display panel. Review your wiring.
3 The detector goes into its FAULT state when supply voltage drops under
16.5V. The detector status goes back to NORMAL, when the supply voltage is
above 17.5V.
4 Detector Inspection: Visually inspects the viewing window of the detector. It
should be clean and clear. The POWER LED should be ON and the ALARM
LED should be OFF. The ALARM should be OFF and the FAULT relay should
be ON. The 4-20mA Output should be 5mA.
5 If any of the outputs or indications is different from the description in step 4,
see paragraph 8.6.1 for troubleshooting.
The Flame Detector is now ready for Functional Testing.
7.3 Reset
If the optional alarm latching mode has been selected, RESET of a detector, when
in its ALARM state, can be activated by disconnecting power (terminal No. 1 or
terminal No. 2), or initiating a manual BIT.
7.4 Functional testing
Following is a test procedure for proper functioning of the detector. The detector
can be tested using the Manual Built-in-Test (BIT) or the Spectrex IR3 Fire
Simulator - 20/20-310