Spectrex 20/20CTIN-CTIP Flame Detector User Manual
Page 52
Spectrex Inc. - SharpEye
TM
CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005
44
CCTV Wire Type
The wire for the video picture must be Twisted Pair Wire.
Network Wiring
UTP
Wire Gauge
24 AWG or thicker
Category Type
2, 3, 4, 5 or better
Impedance 100±200
ohms
DC Loop Resistance
52 ohms per 1,000ft (300m)
Differential Capacitance
19pF/ft
max
The Twist Pair must be connected to a PASSIVE or ACTIVE receiver depending
on the length cable from the CCTV to the receiver.
0 - 1000 ft (300m)
Require PASSIVE receiver
660 - 3300 ft (200m - 1000m)
Require ACTIVE receiver
The connection from the receiver should be made by coax cable connected to the
monitor or through a switching box when connecting two (2) or more CCTVs to the
same monitor.