3. Performance

3.1 Detection Sensitivity

A. Flame

Detection sensitivity is the maximum distance at which the detector will reliably
detect a specific size of fire & typical type of fuel (standard fire).


Standard Fire:
A 1ft x 1ft (0.3m x 0.3m) Gasoline pan fire with max. wind speed of 6.5 ft/sec
(2 m/sec).

Sensitivity Ranges:
The detector has four user selectable sensitivity ranges. For each range there are
two response levels.

1. WARNING (Pre-alarm)
2. ALARM


The detection distance, for the WARNING level, is approximately 10% longer than
the ALARM distance. Alarm response times for a “standard fire” at a specified
range are shown hereunder.

Table 1: Alarm Response Time Versus Range

Sensitivity

1

2

3

4

Range – ft (m)

50 (15)

100 (30)

150 (45)

200 (60)

Response Time (sec)

3 5 8 10

For some typical ambient conditions the Zeta parameter as defined in NFPA 72 for
the detector is 0.005 (1/meter).

Note:

Zeta parameters may vary significantly with changes in temp, air pressure,
humidity, visibility conditions, etc.