7

Other fuels
The detector will react to other types of fires as follows:
Pan Fire Size: 1ft x 1ft (0.3m x 0.3m)
Maximum Wind Speed: 6.5 ft/sec (2 m/sec)
Maximum Response Time: 10 sec

Table 2: Response Sensitivity Ranges

Type Of Fuel

% Of Max. Distance at

Each Sensitivity Range

Gasoline 100%
N-Heptane 100%
Alcohol 95%

75%

JP4 75%
Kerosene 75%
Diesel Fuel

70%

Methane* 30%
Propane* 30%

* 0.5m plume fire



B. CCTV
The CCTV picture enables the user to identify a 1x1 foot gasoline flame from a
distance of 100 feet (30 meters) offering a “live video” image of the monitored