CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005

45

Appendix C – RS-485 Communication Network


Using the RS-485 network capability of the IR3 detector and additional software it
is possible to connect up to 32 detectors in an addressable system with 4 wires
only (2 for power & 2 for communication). Using repeaters, the number of
detectors can be much larger (32 detectors for each repeater) up to 247 on the
same 4 wires. When using the RS-485 network it is possible to read each detector
status (FAULT, WARNING, ALARM) and to initiate a BIT to each detector
individually.

Fore more details, consult the factory.

Figure 15: RS-485 networking