CCTV Model Flame Detector Manual – TM 788100, Rev. A January 2005

11

4.2 Output Signals

The detector controls the following outputs:

• Alarm relay

• Accessory relay

• Fault relay

• 4-20mA current output

• RS-485 communication


The detector can be in one of the following states.

Normal:

The detector is functioning normally.

BIT:

The detector performs a Built-In-Test.

Warning:

Fire detected - changed to warning – pre-alarm state.

Alarm:

Fire detected - changed to fire alarm state.

Latched Alarm
(Optional)

The alarm outputs are latched due to the detection of a fire that
has already been extinguished.

Fault:

A fault is detected during a BIT sequence or the power supply is
too low. In each state the detector will activate different outputs
as specified in table 6.

Table 6: Output Signals Versus Detector State

Detector
State

Power
Led

Alarm
Led

Alarm
Relay

Accessory
Relay

Fault
Relay

4-20mA
Output

Normal

On Off

Off Off

On

5mA

Warning

On Flash

2Hz

Off On

On 10mA

Alarm

(4)

On On On On

On 15mA

Latch

(2)

On Off On Off

On

5mA

Fault

(3)

Flash
4Hz

Off Off Off

Off

0mA


Note:
1. The video output can be activated continuously or only when a fire is detected,

according to programmable function. See Table 8

2. The Alarm state can be latched, according to programmable function
3. The detector will be in its BIT FAULT state until it has passed a successful BIT.
4. The alarm outputs will be activated as long as the alarm conditions are present

and will stop approximately 5 seconds after the fire is no longer detected.