beautypg.com

Spectrex 20/20MU - Mini Flame Detector User Manual

Page 36

background image

Spectrex Inc. - SharpEye

TM

ML & MU Flame Detector Manual – TM 767100, Rev. A, April 2005

28

4-20 mA Output
This output is used for analog, 4-20 mA current output as specified in
Paragraph 5.1D
PIN No. 11 or pink wire - output (+).
PIN No.12 or blue wire -input (-)
See Appendix A for more details.

RS-485
This output is used for communication network as specified in Appendix A.
PIN No. 10 or white wire - positive (+) lead.
PIN No. 9 or gray wire - negative (-) lead.

Ground
Pin No. 12 or green wire - Ground connection.

6.7 Operation Mode

The detector is supplied with a default function set up (see table 8). The function
set up can be reprogrammed by the user through RS-485 using a PC with
Spectrex Host Software or through use of a handheld unit. Refer to TM 784050 for
instructions.

Programmable Function:
Modes of operation are programmable with a PC or Handheld unit according to the
selection table in Paragraph 4.3.2 and Refer to TM 784050.

Address:
The detector has the capability of acting as an addressable device.
The detector provides 247 (1-247) addresses, which can be used by the RS-485
communications link as described in paragraph 4.3.2 d - and Refer to TM 784050.

Alarm Delay:
An Alarm Delay may be required for certain applications. The detector has an
Alarm Delay that permits time delays from 0, anti-flare, 3, 5, 10, 15, 20 and 30
seconds respectively. The delay can be defined by the RS-485.
Refer to TM784050.

This manual is related to the following products: