3.3 False Alarms Prevention

The detector will not provide an alarm or a warning signal as a reaction to the
radiation sources specified below.
False alarm immunity is listed in
- Table 2 for the 20/20 ML UV/IR detector
- Table 3 for the 20/20 MU UV detector

Notes:
IAD = Immune at Any Distance.
All sources are chopped from 0 to 20Hz.

Table 2. 20/20ML - Immunity to False Alarm Faults

Radiation Source

Immunity
Distance ft. (m)

Sunlight IAD
Indirect or reflected sunlight

IAD

Vehicle headlights (low beam) conforming to MS53023-1

IAD

Incandescent frosted glass light, 100W

IAD

Incandescent clear glass light, rough service, 100W

IAD

Fluorescent light with white enamel reflector, standard office
or shop, 40W (or two 20W)

IAD

Arc welding [4mm (5/32in) rod; 240A]

9.8ft (3m)

Bright colored clothing, including red and safety orange

IAD

Electronic flash (180 watt seconds minimum output)

IAD

Red dome light conforming to M251073-1

IAD

Blue-green dome light conforming to M251073-1

IAD

Flashlight (Mx 991/U)

IAD

Radiation heater, 1500W

IAD

Radiation heater, 1000W with fan

IAD

Grinding metal

3.3ft (1m)

Lit cigar or cigarette

IAD

Match, wood, stick including flare up

3.3ft (1m)