beautypg.com

Spectrex 20/20MU - Mini Flame Detector User Manual

Page 20

background image

Spectrex Inc. - SharpEye

TM

ML & MU Flame Detector Manual – TM 767100, Rev. A, April 2005

12

Table 3. 20/20MU - Immunity to False Alarm Faults

Radiation Source

Immunity
Distance ft. (m)

Sunlight IAD
Indirect or reflected sunlight

IAD

Vehicle headlights (low beam) conforming to MS53023-1

IAD

Incandescent frosted glass light, 100W

IAD

Incandescent clear glass light, rough service, 100W

IAD

Fluorescent light with white enamel reflector, standard office
or shop, 40W (or two 20W)

IAD

Bright colored clothing, including red and safety orange

IAD

Red dome light conforming to M251073-1

IAD

Blue-green dome light conforming to M251073-1

IAD

Flashlight (Mx 991/U)

IAD

Radiation heater, 1500W

IAD

Radiation heater, 1000W with fan

IAD

Lit cigar or cigarette

5ft. (1.5m)

Match, wood, stick including flare up

13.3ft. (4.0m)

Please Note: UV flame detectors are sensitive to false alarm from UV radiation
sources such transforms, motors, welding, spikes, etc. (That may be present in the
protected area or far away.)