Anti Flare
Anti Flare mode is selected to prevent false alarm in locations where fast
flares may be present. The Time delay for fire alarm in this mode is from 2.5
to 15 seconds (mostly less than 10 seconds).

Table 5: Time Delay

Delay (seconds)

0

*A – anti-flare

3
5

10
15
20
30

* Default

c. Function Setup
The user can select the desired mode of operation by means of host.

Table 6: Function Setup

Name

Yes

No

1

Alarm Latch

Alarm latching enable

Alarm latching disable
(default)

2

Automatic BIT

Automatic & manual BIT
(default)

Manual BIT only

3

Alarm BIT

Successful Manual BIT
activates the Alarm Relay for
approximately 3 seconds; the
4-20mA will provide 20mA for
3 sec

Successful manual BIT
does not activate the
Alarm Relay (default)


d. Addresses Setup

Refer to TM 784050 for instructions for defining the addresses of the
detectors. The detector provides up to 247 addresses (from 1 to 247) that
can be used with RS-485 communication link.