beautypg.com

Spectrex 20/20MU - Mini Flame Detector User Manual

Page 17

background image

Spectrex Inc. - SharpEye

TM

ML & MU Flame Detector Manual – TM 767100, Rev. A, April 2005

9

Other fuels
The detector will react to other types of fires as follows:

Pan Fire Size: 1ft

2

(0.1m

2

)


Maximum Wind Speed: 6.5 ft/sec (2 m/sec)

Maximum Response Time: 10 sec

Table 1: Response Sensitivity Ranges for other fuels

% Of Max. Distance

Type Of Fuel

Fire size

20/20ML

20/20MU

Gasoline 100

100

n-Heptane

100

100

Diesel Fuel

75

75

JP5 75

75

Kerosene 75

75

Alcohol (Ethanol)

50

75

IPA (Isopropyl Alcohol)

50

50

Methanol

1ft

2

(0.1m

2

) pan fire

50 50

Methane 30

80

LPG (Propane)

30

80

Hydrogen

20" (0.5 m) Plume fire

30 100

Silane

12" (0.3 m) Plume fire

30

60

Polypropylene Pellets

8" (0.2 m) Dianeter

30

40

Office Paper

1ft

2

(0.1m

2

) pan fire

25

40

This manual is related to the following products: