Spectrex 20/20MU - Mini Flame Detector User Manual
Page 17
Spectrex Inc. - SharpEye
TM
ML & MU Flame Detector Manual – TM 767100, Rev. A, April 2005
9
Other fuels
The detector will react to other types of fires as follows:
Pan Fire Size: 1ft
2
(0.1m
2
)
Maximum Wind Speed: 6.5 ft/sec (2 m/sec)
Maximum Response Time: 10 sec
Table 1: Response Sensitivity Ranges for other fuels
% Of Max. Distance
Type Of Fuel
Fire size
20/20ML
20/20MU
Gasoline 100
100
n-Heptane
100
100
Diesel Fuel
75
75
JP5 75
75
Kerosene 75
75
Alcohol (Ethanol)
50
75
IPA (Isopropyl Alcohol)
50
50
Methanol
1ft
2
(0.1m
2
) pan fire
50 50
Methane 30
80
LPG (Propane)
30
80
Hydrogen
20" (0.5 m) Plume fire
30 100
Silane
12" (0.3 m) Plume fire
30
60
Polypropylene Pellets
8" (0.2 m) Dianeter
30
40
Office Paper
1ft
2
(0.1m
2
) pan fire
25
40