3. Performance

3.1 Detection Sensitivity

Detection sensitivity is the maximum distance at which the detector will reliably
detect a specific size of fire & typical type of fuel (standard fire).

Standard Fire:
A 1ft

2

(0.1m

2

) Gasoline pan fire with max. wind speed of 6.5 ft/sec (2 m/sec).


Sensitivity Ranges:
The detector has two user selectable sensitivity ranges. For each range there are
two response levels.

1. WARNING (Pre-alarm)
2. ALARM


The detection distance, for the WARNING level, is approximately 10% higher than
the ALARM distance. Alarm response times for a “standard fire” at a specified
range are shown hereunder.

Sensitivity Range – ft (m)

50 (15)

Response Time (sec)

5

For some typical ambient conditions the Zeta parameter as defined in NFPA 72 for
the detector 20/20ML is 0.01 (1/meter) and 20/20MU is 0.0003 (1/meter).

Note:

Zeta parameters may vary significantly with changes in temp, air pressure,
humidity, visibility conditions, etc.