5.Technical Specifications

5.1 Electrical Specifications

A. Operating Voltage: 18-32 VDC
B. Power Consumption:

Max. 35mA in Stand-by

Max. 80mA in Alarm

C. Electric input protection: The input circuit is protected against voltage-

reversed polarity, voltage transients, surges and spikes according to
MIL-STD-1275A.

D. Electrical outputs

Dry Contact Relays:

Table 8: Contact Ratings

Relay
Name

Type

Normal
position

Maximum Ratings

Alarm

SPST N.O.

2A at 30VDC or 0.5A at 250 VAC

Fault *

SPST N.C.

2A at 30VDC or 0.5A at 250 VAC

* The FAULT relay will be normally energized closed during normal operation of the
detector. The contact will be open at Fault condition or low voltage.

4-20mA Current Output:

The 4-20mA is isolated sink option.
The maximum permitted load resistor is 600Ohm.

STATE

20/20ML Output

(mA)

20/20MU Output

(mA)

To

FAULT 0

0

+0.5mA

BIT FAULT

2

2

±10%

NORMAL 4

4 ±10%

IR Detect

8

-

±5%

UV Detect

12

-

±5%

WARNING 16

16

±5%

ALARM

20

20

±5%

Communication Network:

The detector is equipped with an RS-485 communication link that can be
used in installations with computerized controllers. The communications
protocol is Modbus compatible.

This protocol is a standard and widely used.
It enables continuous communication between a single standard

Modbus controller (Master device) and a serial Network of up to 247
detectors.

It enables connection between different types of Spectrex detectors or

other Modbus devices to the same Network.