ML & MU Flame Detector Manual – TM 767100, Rev. A, April 2005
19
5.Technical Specifications
5.1 Electrical Specifications
A. Operating Voltage: 18-32 VDC
B. Power Consumption:
Max. 35mA in Stand-by
Max. 80mA in Alarm
C. Electric input protection: The input circuit is protected against voltage-
reversed polarity, voltage transients, surges and spikes according to
MIL-STD-1275A.
D. Electrical outputs
• Dry Contact Relays:
Table 8: Contact Ratings
Relay
Name
Type
Normal
position
Maximum Ratings
Alarm
SPST N.O.
2A at 30VDC or 0.5A at 250 VAC
Fault *
SPST N.C.
2A at 30VDC or 0.5A at 250 VAC
* The FAULT relay will be normally energized closed during normal operation of the
detector. The contact will be open at Fault condition or low voltage.
• 4-20mA Current Output:
The 4-20mA is isolated sink option.
The maximum permitted load resistor is 600Ohm.
STATE
20/20ML Output
(mA)
20/20MU Output
(mA)
To
FAULT 0
0
+0.5mA
BIT FAULT
2
2
±10%
NORMAL 4
4 ±10%
IR Detect
8
-
±5%
UV Detect
12
-
±5%
WARNING 16
16
±5%
ALARM
20
20
±5%
• Communication Network:
The detector is equipped with an RS-485 communication link that can be
used in installations with computerized controllers. The communications
protocol is Modbus compatible.
This protocol is a standard and widely used.
It enables continuous communication between a single standard
Modbus controller (Master device) and a serial Network of up to 247
detectors.
It enables connection between different types of Spectrex detectors or
other Modbus devices to the same Network.