ML & MU Flame Detector Manual – TM 767100, Rev. A, April 2005
14
4.2 Output Signals
The detector provides the following outputs:
• Alarm relay
• Fault relay
• 4-20mA current output
• RS-485 communication
The detector can be in one of the following states.
Normal:
The detector is functioning normally.
BIT:
The detector performs a Built In Test.
Warning:
Fire detected – warming alarm (pre-alarm) state
Alarm:
Fire detected – fire alarm state
Latched Alarm
(Optional)
The alarm outputs are latched due to the detection of a fire
that has already been extinguished.
BIT Fault:
A fault is detected during BIT sequence. The detector will
continue to detect fire if the alarm conditions occur.
Fault:
A fault is detected when the power supply is too low or
during a software fault.
In each state, the detector will activate different outputs as specified in table 4.
Table 4: Output Signals versus Detector State
Detector
State
Color LED
Flashing
LED
Alarm
Relay
Fault Relay
4-20mA
Output
Normal Green 1
Hz Off On 4
mA
Warning
Red
2 Hz
Off
On
16 mA
Alarm
(1)
Red Steady On On 20
mA
Latch
(2)
Red
Steady
On On 20
mA
BIT Fault
(3)
Yellow
4
Hz
Off
Off
2
mA
Warning at
BIT Fault
Red
2 Hz
Off
Off
16 mA
Alarm at
BIT Fault
Red Steady On
Off 20
mA
Fault Yellow
4
Hz Off Off 0
mA
Notes:
1 The alarm outputs will be activated as long as the alarm conditions are present
2 The Alarm state can be latched (optional) according to programmable function
3 The detector will be in its BIT FAULT state until it has passed a successful BIT
and will stop approximately 3 seconds after the fire is no longer detected.