Pyromation Series 610 1_16 DIN User Manual

Page 93

background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual

Parameter Lower

Display

Upper
Display

Description Default

Value

When
Visible

Retransmit
Output 3 Scale
maximum

+ $

to

Display value where output is maximum

Range
max

0,!=
+!/- or
+!/)

Retransmit
Output 3 Scale
minimum

+ '

to

Display value where output is minimum

Range min 0,!=

+!/- or
+!/)

C

PV is visible in Operator
mode

=-

PV not visible in Operator
mode

Display
Strategy

=,@

-"

Displays

-"

in Operator

mode when Limit Output is
not active

C

Always

-3%

ASCII

Mm

C

Modbus with Even Parity

Comms
Protocol

Mm

Modbus with Odd Parity

Mm

C

@C

=

+

.

1.2 kbps

.

2.4 kbps

.

4.8 kbps

.

9.6 kbps

Bit rate

1=

.

19.2 kbps

.

@C

=

+

A unique address for each
instrument between 1 to 255
(Modbus), or 1 to 99 (Ascii)

@C

=

+

r_

o

3 C

r_

Ww

Always

3' N

 to

Always

Modbus with no parity

Mm

)+ /

Communica-
tions Address

==+

Read only. Comms
writes ignored

Communica-
tions Write
Enable

Read / Write. Writing via
Comms is possible

r_

Ww

Configuration
Mode Lock
Code

Notes:

Option Slot 1 is a fixed Limit Relay output. A Digital Input module, if fitted to Option Slot A
will duplicate the function of the front Reset key . As these functions cannot be
changed, configuration menus are not required.
Alarm parameters marked * are repeated in Setup Mode.

CAUTION:

Process Variable Offset modifies the measured value to compensate for probe
errors. Positive values increase the reading, negative values are subtracted. This
parameter is effectively, a calibration adjustment and MUST be used with care.


Page 88

P6700, P8700& P4700 Model Group

59305, Issue 6 – March 2006