P6100, p6120, p8100 & p4100 controllers –communic, Bit parameters, Word parameters – Pyromation Series 610 1_16 DIN User Manual
Page 63

1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
P6100, P6120, P8100 & P4100 Controllers –Communications Parameters
The Modbus parameter addresses, and the possible ASCII message types and parameter
indents for the P6100, P6120, P8100 & P4100 are detailed below. RO indicates a parameter
is read only, R/W indicates it can also be written to. Communications writes will not
implemented if the Communications Write Parameter is disabled. Refer to the Modbus and
ASCII Communications sections of this manual for details of the protocols used.
Bit Parameters
Bit parameters are not applicable to the ASCII protocol.
Table 14. P6100, P6120, P8100 & P4100 Communications - Bit Parameters
Parameter
Modbus
Parameter No.
Notes
1
RO
1 = Write Enabled, 0 = Write Disabled. A negative
acknowledgement (exception code 3) is sent to write
commands if communications writes are disabled
Auto / Manual
2
R/W 1 = Manual Control, 0 = Automatic Control
3
R/W 1 = Activate(d), 0 = Dis-engage(d)
4
R/W 1 = Activate(d), 0 = Dis-engage(d)
Alarm 1 Status
5
RO
1 = Active, 0 = Inactive
Alarm 2 Status
6
RO
1 = Active, 0 = Inactive
Setpoint Ramping
7
R/W 1 = Enable(d), 0 = Disable(d)
Loop Alarm Status
10
R/W 1 = Active/Enable, 0 = Inactive/Disable
Loop Alarm
12
R/W Read to get loop alarm status. Write 0/1 to
disable/enable.
Digital Input 2
13
RO
State of Option B digital input.
To set the bit value to 1 write FF, to set the bit value to 0 write 00. Refer to Function Code 05 in the
Modbus Communications section.
Word Parameters
Table 15. P6100, P6120, P8100 & P4100 Communications - Word Parameters
Parameter
Modbus
Parameter No.
ASCII Ident &
Message Types
Notes
Current value of PV.
If under-range = 62976 (?>5 ASCII)
If over-range = 63232 (?>0 ASCII)
1
RO
M
Type 2
RO
If Sensor break = 63488 (ASCII = n/a)
2
R/W
S
Type 2
Type 3/4
RO
R/W
Value of currently selected setpoint.
(Target setpoint if ramping).
Parameter is read only if the current
setpoint is RSP.
Output Power
3
R/W
W
Type 2
Type 3/4
RO
R/W
0% to 100% for single output;
−100%
to +100% for dual output control.
Read Only if not in manual control.
Deviation
4
RO
V
Type 2
RO
Difference between Process Variable
and Setpoint (value = PV-SP)
Page 58
P6100, P6120, P8100 & P4100 Model Group
59305, Issue 6 – March 2006