1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual

Once the instrument is installed in its mounting panel, it may be subsequently removed from
it’s housing, if necessary, as described in the Fitting and Removing Option Modules section.

Instruments may be mounted side-by-side in a multiple installation, but instrument to panel
moisture and dust sealing will be compromised. The cut-out width (for n instruments) is
shown below.

1

/

8

- &

1

/

16

- DIN Instruments (excluding

1

/

8

- DIN Indicators):

(48n - 4) mm or (1.89n - 0.16) inches.

1

/

4

- DIN Instruments &

1

/

8

- DIN Indicators:

(96n - 4) mm or (3.78n - 0.16) inches

If panel sealing must be maintained, mount each instrument into an individual cut-out with
6mm or more clearance between the edges of the holes.

Note:

The mounting clamp tongues may engage the ratchets either on the sides or the
top/bottom faces of the Instrument housing. When installing several Instruments side-by-
side in one cut-out, use the ratchets on the top/bottom faces.