- DIN Controllers & Indicators - Product Manual

Word Parameters

Table 30. P6010 & P8010 Communications - Word Parameters

Parameter

ASCII Ident &

Message Types

Notes

Current value of PV.

Process Variable

1

M

Type 2

RO

Process Variable
Maximum

2

Process Variable
Minimum

Minimum displayed value since this
was last reset. Shows under/over-
range or break values if appropriate.

Modbus

Parameter No.

If under-range = 62976 (5 ASCII)
If over-range = 63232 (0 ASCII)

RO

Sensor break = 63488 (ASCII = n/a)

RO

A

Type 2

RO

Maximum displayed value since this
was last reset. Shows under/over-
range or break values if appropriate.

3

RO

B

Type 2

RO

Alarm 1 Elapsed
Time

4

RO

T

Type 2

RO

Accumulated alarm 1 active time since
this was last reset. Returns the over-
range value if the time exceeds 1000
minutes. Units = seconds in Modbus

Bit Meaning

0

Alarm 1 status.
0 = activated, 1 = safe

1

Alarm 2 status.
0 = activated, 1 = safe

Instrument Status

5

2

3

This bit always = 1
Alarm 1 latched status.
0 = latched
1 = not latched or non-
latching output type

6

This bit always = 0

Alarm 3 status.
0 = activated, 1 = safe
Change Indicator. 1 =
A parameter other than
instrument status or PV
has changed since the
last time the status
word was read.

4
5

RO

L

Type 2

RO

7

This bit always = 0

Process Variable
Offset

6

R/W

J

Type 2, 3/4

R/W

Modified PV = Actual PV + PV Offset.
Limited by Scale Range Maximum
and Scale Range Minimum.

Alarm 1 Value

7

R/W

C

Type 2, 3/4

R/W

Alarm 1 active at this level

Alarm 2 Value

8

R/W

E

Type 2, 3/4

R/W

Alarm 2 active at this level

Alarm 3 Value

9

R/W

N

Type 2, 3/4

R/W

Alarm 3 active at this level


59305, Issue 6 – March 2006

P6010 & P8010 Model Group

Page 115