Pyromation Series 610 1_16 DIN User Manual
Page 72

1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
Parameter Lower
Display
Upper
Display
Description Default
Value
When
Visible
)?
Range Min. to Range Max.
Parameter repeated in Setup Mode
Range
Max.
'=
):$
)'
Range Min. to Range Max
Parameter repeated in Setup Mode
Range
Min.
'=
):'
='
±span from setpoint
Parameter repeated in Setup Mode
'=
=
'
1 LSD to full span from setpoint.
Parameter repeated in Setup Mode
'=
C=
$4
1 LSD to 100% of span (in display units)
on “safe” side of alarm point.
Parameter repeated in Setup Mode
Always
Alarm 2 Type
'
As for alarm 1 type
):'
Always
)?
Range Min. to Range Max.
Parameter repeated in Setup Mode
Range
Max.
'=
):$
)'
Range Min. to Range Max.
Parameter repeated in Setup Mode
Range
Min.
'=
):'
='
±span from setpoint.
Parameter repeated in Setup Mode
'=
=
'
1 LSD to full span from setpoint.
Parameter repeated in Setup Mode
'
=
C=
$4
1 LSD to 100% of span (in display units)
on “safe” side of alarm point.
Parameter repeated in Setup Mode
Always
' C
=, (disabled) or
C (enabled)
=,
Always
C C!
No alarms Inhibited
'
Alarm 1 inhibited
'
Alarm 2 inhibited
%C?
/?
Alarm 1 and alarm 2
inhibited
C C!
Always
59305, Issue 6 – March 2006
P6170, P8170 & P4170 Model Group
Page 67