beautypg.com

Pyromation Series 610 1_16 DIN User Manual

Page 90

background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual

Parameter Lower

Display

Upper
Display

Description Default

Value

When
Visible

(3

N type: 0 to 1399 ºC

("

N type: 32 to 2551 ºF

+3

R type: 0 to 1759 ºC

+"

R type: 32 to 3198 ºF

-3

S type: 0 to 1762 ºC

-"

S type: 32 to 3204 ºF

/3

T type: -240 to 400 ºC

/"

T type: -400 to 752 ºF

/

.

3

T type: -128.8 to 400.0 ºC
with decimal point

/

.

"

T type: -199.9 to 752.0 ºF
with decimal point

)3

PtRh20% vs PtRh40%:
0 to 1850 ºC

)"

PtRh20% vs PtRh40%:
32 to 3362 ºF

).3

Pt100: -199 to 800 ºC

)/"

Pt100: -328 to 1472 ºF

)/

.

3

Pt100: -128.8 to 537.7 ºC
with decimal point

)/

.

"

Pt100: -199.9 to 999.9 ºF
with decimal point

:

0 to 20mA DC

:

4 to 20mA DC

:

0 to 50mV DC

.

10 to 50mV DC

:

0 to 5V DC

:

1 to 5V DC

:

0 to 10V DC

Input type and
Range
(Continued)

:

2 to 10V DC

63

for Europe

6"

for USA

Always

Scale Range
Upper Limit

+1'

Scale Range Lower Limit +100 to Range
Max

Linear
inputs =
1000
(°C/°F =
max
range)

Always

Scale Range
Lower Limit

+''

Range Min. to Scale range Upper Limit -
100

Linear = 0
(°C/°F =
min range)

Always


59305, Issue 6 – March 2006

P6700, P8700& P4700 Model Group

Page 85

This manual is related to the following products: