P6170, P8170 & P4170 Controllers – Serial Communications Parameters
The P6170, P8170 & P4170 communications parameters are detailed in the following tables.
RO indicates a parameter is read only, R/W indicates it can also be written to. Writes will not
implemented if the Communications Write parameter is disabled.
Note:
These models support the Modbus protocol. Refer to the Modbus Communications section
for information on message types. The older ASCII protocol is not supported..
Bit Parameters
To set the bit value to 1, write FF. To set the bit value to 0, write 00.
Refer to Function Code 05 in the Modbus Communications section for bit writes.
Table 19. P6170, P8170 & P4170 Communications - Bit Parameters
Parameter
Modbus
Parameter No.
Notes
1
RO
1 = Write Enabled, 0 = Write Disabled. A negative
acknowledgement (exception code 3) is sent to write
commands if communications writes are disabled
Auto / Manual
2
R/W
1 = Manual Control, 0 = Automatic Control
3
R/W
1 = Activate(d), 0 = Dis-engage(d)
R/W
1 = Activate(d), 0 = Dis-engage(d)
Alarm 1 Status
5
RO
Alarm 2 Status
6
RO
1 = Active, 0 = Inactive
7
R/W
1 = Enable(d), 0 = Disable(d)
Loop Alarm Status
10
1 = Active/Enable, 0 = Inactive/Disable
Loop Alarm
12
R/W
Read for loop alarm status. Write 0/1 to Disable/enable.
Digital Input 2
13
RO
State of Option B digital input.
15
R/W
1 = Enable(d), 0 = Disable(d)
4
1 = Active, 0 = Inactive
Setpoint Ramping
R/W
Auto Pretune
Word Parameters
Table 20. P6170, P8170 & P4170 Communications - Word Parameters
Parameter
Modbus
Parameter No.
Notes
RO
Current value of PV. Under-range = 62976, over-range =
63232, Sensor break = 63488
2
Value of currently selected setpoint. (Target setpoint if
ramping). Read only if the current setpoint is RSP.
Deviation
4
RO
Difference between Process Variable and Setpoint
(value = PV-SP)
6
R/W
Adjustable 0.5% to 999.9% of input span. Read only
when Self-Tuning.
7
R/W
1 = Direct Acting, 0 = Reverse
Automatic Reset
Time
8
R/W
Integral Time Constant value.
Adjustable 0 to 5999. Read only if Self-Tuning.
1
R/W
Control Action
Page 80