P6170, P8170 & P4170 Controllers – Serial Communications Parameters

The P6170, P8170 & P4170 communications parameters are detailed in the following tables.
RO indicates a parameter is read only, R/W indicates it can also be written to. Writes will not
implemented if the Communications Write parameter is disabled.

Note:

These models support the Modbus protocol. Refer to the Modbus Communications section
for information on message types. The older ASCII protocol is not supported..

Bit Parameters

To set the bit value to 1, write FF. To set the bit value to 0, write 00.
Refer to Function Code 05 in the Modbus Communications section for bit writes.

Table 19. P6170, P8170 & P4170 Communications - Bit Parameters

Parameter

Modbus

Parameter No.

Notes

Communication
Write Status

1

RO

1 = Write Enabled, 0 = Write Disabled. A negative
acknowledgement (exception code 3) is sent to write
commands if communications writes are disabled

Auto / Manual

2

R/W

1 = Manual Control, 0 = Automatic Control

Self Tune

3

R/W

1 = Activate(d), 0 = Dis-engage(d)

Pre tune

R/W

1 = Activate(d), 0 = Dis-engage(d)

Alarm 1 Status

5

RO

Alarm 2 Status

6

RO

1 = Active, 0 = Inactive

7

R/W

1 = Enable(d), 0 = Disable(d)

Loop Alarm Status

10

1 = Active/Enable, 0 = Inactive/Disable

Loop Alarm

12

R/W

Read for loop alarm status. Write 0/1 to Disable/enable.

Digital Input 2

13

RO

State of Option B digital input.

15

R/W

1 = Enable(d), 0 = Disable(d)

4

1 = Active, 0 = Inactive

Setpoint Ramping

R/W

Auto Pretune

Word Parameters

Table 20. P6170, P8170 & P4170 Communications - Word Parameters

Parameter

Modbus

Parameter No.

Notes

Process Variable

RO

Current value of PV. Under-range = 62976, over-range =
63232, Sensor break = 63488

Setpoint

2

Value of currently selected setpoint. (Target setpoint if
ramping). Read only if the current setpoint is RSP.

Deviation

4

RO

Difference between Process Variable and Setpoint
(value = PV-SP)

Primary
Proportional Band

6

R/W

Adjustable 0.5% to 999.9% of input span. Read only
when Self-Tuning.

7

R/W

1 = Direct Acting, 0 = Reverse

Automatic Reset
Time

8

R/W

Integral Time Constant value.
Adjustable 0 to 5999. Read only if Self-Tuning.

1

R/W

Control Action


Page 80

P6170, P8170 & P4170 Model Group

59305, Issue 6 – March 2006