Operation – KROHNE IFC 070 Converter EN User Manual
Page 22
6
OPERATION
22
IFC 070
www.krohne.com
11/2009 - 7311242200 - MA IFC 070 R02
51
Status output 1
Self checking
0
0 = off
Active at instrument failure, e.g. coil,
electrode, battery. Can be reset by
menu no. 72.
1 = on
52
Status output 1
Battery pre
warning
0
0 = off
Active at low battery (10% left). Can be
reset by menu no. 72.
1 = on
53
Status output 1
Battery final
warning
0
0 = off
Active at very low battery (1% left).
Can be reset by menu no. 72.
1 = on
54
Status output 1
Counter overrun
0
0 = off
Active if counter goes from 99999999
to 00000000. Can be reset by menu no.
72.
1 = on
55
Status output 2
Self checking
0
0 = off
Active at instrument failure. Can be
reset by menu no. 72.
1 = on
56
Status output 2
Battery pre
warning
0
0 = off
Active at low battery (10% left). Can be
reset by menu no. 72.
1 = on
57
Status output 2
Battery final
warning
0
0 = off
Active at very low battery (1% left).
Can be reset by menu no. 72.
1 = on
58
Status output 2
Counter overrun
0
0 = off
Active if counter goes from 99999999
to 00000000. Can be reset by menu no.
72.
1 = on
59
Status outputs
pulsating
1
0 = off
Pulse width determined by menu no.
44. Can be reset by menu no. 72.
1 = on
60
Show flow rate
0
0 = off
-
1 = on
61
Show counter
forward
0
0 = off
-
1 = on
63
Show counter
reverse
0
0 = off
-
1 = on
65
Show net counter 1
0 = off
-
1 = on
66
All counters
reset
88888
Set to 00000
After reset display value is back to
88888
Confirm with “>” for 3 seconds
71
Counters
run/stop
1
0 = stop
For service / maintenance purposes,
pulse output also stops.
1 = run
72
All errors reset
0
Set to 1
After reset display value is back to 0
Confirm with “>” for 3 seconds
73
Battery type
2
0 = non (external power supply)
Wrong setting influences battery
lifetime calculation.
1 = single (19 Ah)
2 = dual (38 Ah)
3 = external (76 Ah)
74
Battery capacity
19.000
Value in Ah
-
Software version 4.0.4_
Menu
No.
Description
Display
default
Selection list
Remarks