beautypg.com

Operation – KROHNE IFC 070 Converter EN User Manual

Page 19

background image

OPERATION

6

19

IFC 070

www.krohne.com

11/2009 - 7311242200 - MA IFC 070 R02

6.1 Display and operating elements

6.2 Menu of converter

• To enter the menu, hold the V and Z key for 5 seconds.

i

The display flashes.

• Press the Z key to enter the menu.

i

You see the menu number at the left (12 at the beginning) and the value at the right side of
the display.

• Scroll through the available positions with the V key to the position you want to change.
• Press the Z key to enter the value.

i

The value flashes.

• Use the Z and V key to change the value.
• Hold the Z key for 3 seconds to confirm the new value.
• To leave the programming mode, hold the V key for 3 seconds to store the new value(s). If you

do not want to store the new values, do not touch any key for 60 seconds.

Other functions:

• software version: press Z key for 1 second
• display test: press Z key twice for 1 second

1 battery status
2 optical key V to navigate through the menu and to scroll through the measuring pages
3 reset button (only accessible with removed cover)
4 flow direction
5 measured value and measuring unit
6 optical key Z to navigate through the menu