Operation – KROHNE IFC 070 Converter EN User Manual
Page 21
OPERATION
6
21
IFC 070
www.krohne.com
11/2009 - 7311242200 - MA IFC 070 R02
Software version 4.0.4_
Menu
No.
Description
Display
default
Selection list
Remarks
12
Measuring unit
0
0 = m
3
/h
Customer defined
1 = USG/min
2 = l/s
13
Access control
0
0 = Standard
Fiscal metering blocks menu, refer to
figure above this table.
1 = Fiscal metering
20
Meter type
0
0 = WATERFLUX 3070
Select "0" in case of a square cross
section, select "1" in case of a round
cross section.
1 = OPTIFLUX 2070
21
Meter size
100
Defined at factory calibration Choose from table, in chosen unit
(menu no. 12).
22
Meter constant
01.000
Defined at factory calibration
Meter constant is shown on typeplate.
23
Zero offset
calibration
0
Set to 1
In situ determination of zero point.
Confirm with “>” for 3 seconds
After countdown meter switches to
measuring mode.
Menu no. 24 is automatically set to 1.
24
Zero selection
0
0 = factory calibration
Selection which zero point to use
1 = measured
25
Flow direction
0
0 = Forward
-
1 = Reverse
26
Measuring rate
15
1, 5, 10, 15, 20 seconds
Measurement interval in seconds
27
Low flow cut off
10
0, 5, 10 mm/s
Measurements below this value are
neglected
28
Time constant
flow reading
2
1 = fast,
Time constant of display
2 = normal
3 = slow
30
Self check
0
0 = off
Is automatically switched on at fiscal
metering (menu no. 13 = 1)
1 = on
31
Empty pipe
detection
0
0 = off
If switched on, display shows "- EP -".
See graph below this table.
1 = on
32
Simulate outputs
0
0 = off
If set to on, display shows 0 and 1
alternately (independent of setting in
menu no. 41/42). Set to "0" to stop the
simulation.
1 = on (1 pulse per second)
41
Output A (pulse)
0
0 = off
Set pulse rate in menu no. 45
1 = on
42
Output B (pulse)
0
0 = off
Set pulse rate in menu no. 45
1 = on
43
Phase shift
between pulse
outputs
90
90 degrees offset
180 degrees offset
F-r ( A - forward flow, B - reverse
flow)
44
Pulse width
1
1, 5, 10, 50, 100 ms
Choose from table
45
Pulse value
00.100
in m3/pulse or 100 USG/pulse
-