Installation and operating instructions DW 181 - 184

13

4 Display

4.1

Local Flow indication


Indicator “G”

Indicator “A”


All flow switches can be equipped with
indicator G. Scale marks are from 1 to 10 to
allow visual control of the flow rate. The
switching point may be changed as and when
required.


The DW 181, DW 182 and DW 183 flow
switches up to meter size DN100 (4”) can be
supplied with indicator A. The dial is marked in
flow units (e.g. l/h, m³/h) to provide more
accurate flow readings. The switching points are
factory marked on the dial. With this indicator it
is also possible to adjust the switching points at
non-flowing conditions.


High-temperature versions
are supplied without a local indicator.

4.2 Limit

Switches


Every flow switch can be equipped with either one or two limit switches which can be adjusted over
the entire measurement range.

Limit switch specifications

Type and number of switches

Switch rating

Standard
K1(K2) single (twin for K2) bi-stable limit switch

14VA max. (max. 350 V AC, max. 0.4 A)

reed type IA42 ATF 15-45

EExi safety values

Ii < 500mA, Ci = 0 nF, Li = 0 µH

With change over

K1(K2) single (twin for K2) bi-stable limit switch

3 VA max. (max. 28 V DC, max. 0.25 A)

type reed CM21…

EExi safety values

Ii< 500 mA, Ci= 0 nF, Li= 0 µH

With relay

KV1 (KV2)

2000 VA max. (max. 250 V AC, max. 8 A)

Power supply: 240/110/48/24 V AC (50/60 Hz)

110/48/24 V DC

relay type Finder

Response time: 5…12ms

EEx d values

See section 4.3: EEx d version

High-temperature version (non-EEx)
single bi-stable limit switch

18 VA max. (max. 220 V, max. 0.8 A)
reed type IA13….

The switch ratings are given for standard resistance loads. Make sure you use the correct
protection circuits when using other types of load (e.g. inductive).