The full and empty adjustment was carried out

directly in the sensor. The following values are

outputted:

- max. volume (display max.) 20 mA = 2650 l

- min. volume (display min.) 4 mA = 50 l

l

Relay 1 should switch on an emptying pump at a

level of 90 % and switch off the pump at a level of

10 %

1 Select the following functions with the rotary switch.
2 Push one of the two [+/-] adjustment keys, the digital

indication flashes (if the rotary switch is set to

"OPERATE", the [+/-] keys are inoperable).

3 Adjust the requested value with the [+/-] keys. If you

hold the key pushed, the digital indication changes

the value more quickly.

4 Save your settings by pushing the [+/-] keys

simultaneously.

à

Set the function switch to position [8]. Select with the

[+/-] keys the measured value output 4 … 20 mA or

0 … 20 mA. For this example, choose 4 – 20.

The displayed numbers have the following meanings:

l

0 – 20 = 0 … 20 mA

l

4 – 20 = 4 … 20 mA

à

Save the value by pushing the [+/-] keys simultan-

eously.

To scale the indication of SU 600, the filling volumes for

0 % and 100 %. The vessel does not have to be filled or

emptied.
1 Set the function switch to position [7] (display min.).
2 Set the value to 50 via the [+/-] keys.
3 Save the value by pushing both keys simultaneously.
1 Set the function switch to position [6] (display max.).
2 Set the value to 2650 via the [+/-] keys.
3 Save the value by pushing both keys simultaneously.

General procedure

Current output

Scaled indication at 0 %

Scaled indication at 100 %

SU 600 - 4 … 20 mA signal conditioning

25

Setup with the integrated indicating and adjustment unit