Furthermore you have to distinguish between the relay

modes overfill and dry run protection. You switch over by

exchanging the ON/OFF values of the relay.

l

Overfill protection: Relay is switched off when the

max. level is exceeded (safe currentless condition),

relay is switched on again when the level falls below

the min. level (switch on point < switch off point).

l

Dry run protection: Relay is switched off when the

level falls below the min. level (safe currentless

condition), relay is switched on again when the max.

level is exceeded (switch on point > switch off point).

à

To adjust the on and off switching points of relay 1,

set the function switch to position [1] or [2], enter the

switching points for ON or OFF and save your

settings. If necessary, proceed in the same way with

relay 2 (position [3] or [4]).

2

1

3

off (on)

on (off)

o n

o n

o f f

o f f

t

L E D

1 Level

2 Mode overfill protection

3 Mode dry run protection

22

SU 600 - 4 … 20 mA signal conditioning