4 Mounting

4.1 General instructions

You can mount theSU 600 signal conditioning instru-

ment onto a carrier rail 35x7.5 acc. to DIN EN 50022, or

directly on the wall by means of the three screws or in a

front panel or door of a switching cabinet.

4.2 Mounting information

1 Place the adapter plate [1] to the rear of SU 600

(spring of the adapter plate downward) and fasten

the plate with screw [2] (M4x6).

2 PlaceSU 600 against the carrier rail [3] from below

and push the instrument upward until it snaps in.

61

43,5

2

1

3

Fig. 2: Carrier rail mounting
1 Adapter plate

2 Screw (M4x6)

3 Carrier rail

1 Insert the metal strap [1] from above into the housing

cut-out.

2 Fasten the instrument directly to the wall with the

three screws (ø max. 4 mm).

Installation location

Carrier rail mounting

Wall mounting

SU 600 - 4 … 20 mA signal conditioning

11

Mounting