2 setup procedure – KROHNE SU 600 EN User Manual
Page 19
l
[Function switch] for selection of:
- Adjustment
- Relay switching points
- Scaling
- Current output
- Integration time
- Offset correction
-
Current input active/passive
l
[+/-] key:
-
Change value of the parameter
By pushing the [+/-] key, you change the individual
parameters of the selected function. In this phase, the
processed parameter is flashing. By briefly pushing the
two keys simultaneously, you save your settings. "Save"
is briefly displayed.
6.2 Setup procedure
Setup encompasses mainly the adjustment of the
measurement loop. A scaling of the measured value for
the LC display and the adaptation of the relay switching
points are additional settings. Additional setup steps
might be, if necessary, setting an integration time to
smooth the measured value or modifying the current
output characteristics.
To clearly denote the measuring unit, the supplied labels
can be inserted in the cover. In case several SU 600 are
used, each measurement loop should be clearly
labelled.
After being switched on, SU 600 first of all carries out a
short self-check. The following steps are carried out:
l
Internal check of the electronics
l
indication of the firmware version
l
the output signal jumps briefly to the set fault current
Then the actual measured value is displayed and the
corresponding current is transmitted to the current
output.
Key functions
Set up
Switch on phase
SU 600 - 4 … 20 mA signal conditioning
19
Setup with the integrated indicating and adjustment unit
30652
-EN
-050525