KROHNE UFM 3030 EN User Manual

Page 22

background image


22

UFM

3030

4.07.01

PULSE/UNIT

Pulse value for volume flow rate unit, see Function 3.05.09

4.07.02

PULSE/UNIT

Pulse value for heat power rate unit, see Function 3.05.10

4.08.00

PULS WIDTH

Pulse output pulse width incorrect
Ensure condition pulse width

≤ 0.5 x pulse period time is met.

4.08.01 PULS

WIDTH

Pulse width for frequencies

≤ 10 Hz, see Function 3.05.11

4.09.00 HART

Current

output

range for HART incorrect. If Hart is activated the

minimum possible current should be 4 mA.
Ensure condition CURR 0 pct

≥ 4 mA is met.

4.09.01 CURR

RANGE

Range of current output, see Function 3.04.03

4.09.02

CURR 0 pct

Current value for 0% scale, see Function 3.04.04

4.10.00

INP/OUTP

The digital input (C) and current output (I) are not allowed to be
switched on simultaneously. If the Profibus option is activated only
one of the following input/output functions can be used: digital input
(C), current output (I), pulse output (P). The current output is
deactivated by setting the function of current output to off en setting
the range of current output to 0-20mA.

4.10.01

INP FUNCT

Function of digital input, see Function 3.06.01

4.10.02

CURR FUNCT Function of current output, see Function 3.04.01

4.10.03 CURR

RANGE

Range of current output, see Function 3.04.03

4.10.04

PULS FUNCT

Range of pulse output, see Function 3.05.01

4.13.00

EPROM

EPROM checksum error, reset device.