3.04.02 DIRECTION Direction of current output
FORWARD (forward flow measurement)
BOTH (forward and reverse flow measurement indicating both in
the same range)
F/R SPEC (forward and reverse flow measurement indicated in
different range see Function 3.04.04)
3.04.03 RANGE
Range
of current output
OTHER (user defined, see Function 3.04.04 through 3.04.06)
0-20/22 mA (0 pct - 100 pct / limit)
4-20/22 mA(0 pct - 100 pct / limit)
3.04.04
0 pct
Current value for 0% scale
Range: 0 through 16 mA
3.04.05
100 pct
Current value for 100% scale
Range: 4 through 20 mA
Value must be at least 4 mA greater than current value for 0%
scale
3.04.06
LIMIT
Limitation of current value
Range: 20 through 22 mA
3.04.07 ERR
INDIC IERR = 3.6 MA
IERR = 21.5 MA
(only available for NAMUR devices)
3.05.00 PULSE
OUTP
Submenu 3.05.00 Pulse output
3.05.01 FUNCTION Function of pulse output
OFF (switched off)
ACT FLOW (actual flow)
CORR FLOW (corrected flow), see Function 3.02.01 and 3.02.08
through 3.02.11
F/R IND (forward/reverse flow indication)
VOS (velocity of sound, range defined in Function 3.01.11 and
3.01.12)
DIG OUTPUT (digital output, see Function 3.05.03)
BATCH OUTP (batch output indication, see Function 3.02.01)
GAIN (sensor signal gain, range is 0 dBV through 100 dBV)
AN INP 1 (analog input 1)
AN INP 2 (analog input 2)
3.05.02 DIRECTION Direction of pulse output
FORWARD (forward flow measurement)
BOTH (forward and reverse flow measurement indicating both in
the same range)
3.05.03
DIG OUTPUT
Function of digital output
PATH ERR (measuring path error indication)
TOTAL ERR (Totalizer error indication)
ALL ERR (indication of all errors)
AN INP ERR (analog input error indication
OVERRANGE (overrange indication)
TRIP POINT (trips when actual flow (Q) goes over a set limit)
3.05.04
TRIP PNT 1
First trip point
Range: 0 through 120% of Q100%
3.05.05
TRIP PNT 2
Second trip point
Range: 0 through 120 % of Q100%
3.05.06
TIME CONST
Time constant of pulse output 25 ms
MASTER TC (see Function 3.01.04)
3.05.07
OUTPUT
Unit of pulse output (see Function 1.03.00)
PULSE FREQUENCY, pulses per unit time, see Function 3.05.08)
PULSE/UNIT, Totalizer pulse output, pulses per unit volume, see