beautypg.com

%oa mode – KANOMAX 2211 Handheld IAQ Monitor User Manual

Page 20

background image

15

5. %OA Mode

OA MODE is to provide calculation of ventilation ratio with temperature or CO

2

.

Calculation is based on below formula:

%OA(R_A - S_A)(R_A – O_A)×100

* %OA: Ventilation Ratio

R_A: Temperature and CO

2

in respiratory air

S_A: Temperature and CO

2

in supplied air

O_A: Temperature and CO

2

in open air


Measurements take place in order of :
Respiratory Air – Supplied Air- Open Air




















The average value in each point is used for the calculation of ventiltation ratio..
Temperature or CO

2

concentration velue of each point (TRIAL(1)~TRIAL(N)) will be stored in the memory.


TRIAL(1) (2) (3) (N) TRIAL(1) (2) (3) (N) TRIAL(1) (2) (3) (N)

Time needed to measure at a point・・・Sampling Time × N(Number of Trial)

Respiratory (R_A) Supplied (S_A) Open Air (O_A)

Respiratory Air: R_A=ΣTRIAL(N)/N
Supplied Air: S_A=ΣTRIAL(N)/N
Open Air: O_A=ΣTRIAL(N)/N

** Ventilation Ratio (%OA)

%OA = (R_A - S_A) / (R_A - O_A) x 100

Open Air (O_A)

Respiration (R_A)

Supplied (S_A)