Programming Sequence (Relay 1)

On the Con TROLL PRO, select Menu, Settings, Outputs, Relays, Relay 1.

Enable the relay.

Mode = Low Alarm

Parameter = A-Concentration

Setpoint = 4 mg/L

Deadband = 0.2 mg/L (This value is recommended to prevent relay chatter.)

Adjust the Setpoint and Deadband to optimize aerator
performance and minimize aerator cycling.

Programming Sequence (Relay 2)

On the Con TROLL PRO, select Menu, Settings, Outputs, Relays, Relay 2.

l

Enable the relay.

l

Mode = Low Alarm

l

Parameter = B-Concentration

l

Setpoint = 5 mg/L

l

Deadband = 0.2 mg/L (This value is recommended to prevent relay chatter.)

Adjust the Setpoint and Deadband to optimize aerator
performance and minimize aerator cycling.